MODEL
GENERAL
| UPS Type | Rack / Tower |
| Phase | Single phase with ground |
| Rating (VA) | 1000 |
| Nominal Power (W) | 1000 |
| Dimension (mm) | 410 x 438 x 88 (D x W x H) |
| Weight (kg) | 14.1 (with battery)
7.8 (without battery) |
INPUT
| Connection Type | IEC 320-C14 |
| Nominal Voltage | 200/208/220/230/240 VAC |
| Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
| Frequency Range | 40Hz ~ 70Hz |
| Power Factor | ≧0.99 |
| Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
| Connection Type | 8 x IEC 320-C13 |
| Nominal Voltage | 200*/208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
| Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 5 seconds |
| Low Battery | Sounding every 2 seconds |
| Overload | Sounding every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Type | 12V / 7Ah |
| Numbers | 3 |
| Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
| Charging Current | Default 2A, max 12A adjustable |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | Single phase with ground |
| Rating (VA) | 1500 |
| Nominal Power (W) | 1500 |
| Dimension (mm) | 410 x 438 x 88 (D x W x H) |
| Weight (kg) | 15.5 (with battery)
8.1 (without battery) |
INPUT
| Connection Type | IEC 320-C14 |
| Nominal Voltage | 200/208/220/230/240 VAC |
| Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
| Frequency Range | 40Hz ~ 70Hz |
| Power Factor | ≧0.99 |
| Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
| Connection Type | 8 x IEC 320-C13 |
| Nominal Voltage | 200*/208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
| Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 5 seconds |
| Low Battery | Sounding every 2 seconds |
| Overload | Sounding every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Type | 12V / 9Ah |
| Numbers | 3 |
| Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
| Charging Current | Default 2A, max 12A adjustable |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | Single phase with ground |
| Rating (VA) | 2000 |
| Nominal Power (W) | 2000 |
| Dimension (mm) | 630 x 438 x 88 (D x W x H) |
| Weight (kg) | 10.6 (without battery)
23.3 (w/built-int battery) |
INPUT
| Connection Type | IEC 320-C20 |
| Nominal Voltage | 200/208/220/230/240 VAC |
| Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
| Frequency Range | 40Hz ~ 70Hz |
| Power Factor | ≧0.99 |
| Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
| Connection Type | 8 x IEC 320-C13 |
| Nominal Voltage | 200*/208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
| Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 5 seconds |
| Low Battery | Sounding every 2 seconds |
| Overload | Sounding every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Type | 12V / 7Ah |
| Numbers | 6 |
| Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
| Charging Current | Default 2A, max 8A adjustable |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | Single phase with ground |
| Rating (VA) | 3000 |
| Nominal Power (W) | 3000 |
| Dimension (mm) | 630 x 438 x 88 (D x W x H) |
| Weight (kg) | 27.5 (with battery)
12.4 (without battery) |
INPUT
| Connection Type | IEC 320-C20 |
| Nominal Voltage | 200/208/220/230/240 VAC |
| Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
| Frequency Range | 40Hz ~ 70Hz |
| Power Factor | ≧0.99 |
| Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
| Connection Type | 8 x IEC 320-C13
1 x IEC 320-C19 |
| Nominal Voltage | 200*/208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
| Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 5 seconds |
| Low Battery | Sounding every 2 seconds |
| Overload | Sounding every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Type | 12V / 9Ah |
| Numbers | 6 |
| Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
| Charging Current | Default 2A, max 8A adjustable |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 1 phase in / 1 phase out |
| Rating (VA) | 6000 |
| Nominal Power (W) | 6000 |
| Standard Model
Dimension (mm) |
UPS Unit: 610 x 438 x 88 [2U] (D x W x H)
Battery Pack: 600 x 438 x 133 [3U] (D x W x H) |
| Weight (kg) | UPS Unit: 17
Battery Pack: 57 |
| Long-run Model
Dimension (mm) |
610 x 438 x 88 [2U] (D x W x H) |
| Weight (kg) | 17 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 208/220/230/240 VAC VAC |
| Voltage Range | 110~300VAC ± 3% at 50% load
176~300VAC ± 3% at 100% load |
| Frequency Range | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
| Power Factor | ≧0.99 |
| THDi | < 4% @100% Load
< 6% @50% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦1% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 7Ah |
| Numbers | 20 |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Long-run Model
Type |
Depending on applications |
| Numbers | 16 - 20 ** |
| Charging Current (max) | 4.0 A |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 1 phase in / 1 phase out |
| Rating (VA) | 10000 |
| Nominal Power (W) | 10000 |
| Standard Model
Dimension (mm) |
UPS Unit: 610 x 438 x 88 [2U] (D x W x H)
Battery Pack: 600 x 438 x 133 [3U] (D x W x H) |
| Weight (kg) | UPS Unit: 20
Battery Pack: 63 |
| Long-run Model
Dimension (mm) |
610 x 438 x 88 [2U] (D x W x H) |
| Weight (kg) | 20 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 208/220/230/240 VAC VAC |
| Voltage Range | 110~300VAC ± 3% at 50% load
176~300VAC ± 3% at 100% load |
| Frequency Range | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
| Power Factor | ≧0.99 |
| THDi | < 4% @100% Load
< 6% @50% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 208*/220/230/240 VAC |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦1% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 20 |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | 16 - 20 ** |
| Charging Current (max) | 4.0 A |
REAR PANEL
|