MODEL
GENERAL
| UPS Type | Rack / Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 10000VA |
| Nominal Power (W) | 10000W |
| Standard Model
Dimension (D x W x H) (mm) |
UPS unit : 680 x 438 x 133 (3U) Battery Pack : 580 x 438 x 133 (3U) |
| Weight (kg) | UPS unit : 34
Battery Pack : 63 |
| Long-run Model
Dimension (D x W x H) (mm) |
680 x 438 x 133 (3U) |
| Weight (kg) | 34 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 400VAC (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 360/380/400/415 VAC (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 20pcs (10+10) |
| Charging Current (max) | 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable) 12A maximum |
| Charging Voltage | +/-136.5VDC |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | 20pcs (10+10) |
| Charging Current (max) | 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable) 12A maximum |
| Charging Voltage | +/-13.65V*N (N = 10) |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 20000VA |
| Nominal Power (W) | 20000W |
| Standard Model
Dimension (D x W x H) (mm) |
UPS unit : 680 x 438 x 133 (3U) Battery Pack : 580 x 438 x 133 (3U) x 2pcs |
| Weight (kg) | UPS unit : 35
Battery Pack : 63 x 2pcs |
| Long-run Model
Dimension (D x W x H) (mm) |
680 x 438 x 133 (3U) |
| Weight (kg) | 35 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 400VAC (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 360/380/400/415 VAC (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 40pcs (20+20) |
| Charging Current (max) | 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable) 12A maximum |
| Charging Voltage | +/-273VDC |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | 32-40pcs (Adjustable) |
| Charging Current (max) | 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable) 12A maximum |
| Charging Voltage | +/-13.65V*N (N = 16~20) |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 30KVA |
| Nominal Power (W) | 30KW |
|
Dimension (D x W x H) (mm) |
680 x 438 x 133 (3U) |
| Weight (kg) | 29 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 400VAC (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage |
3x 360/380/400/415 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
MANAGEMENT
| Smart RS-232/USB |
Supports Windows, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
BATTERY
| Type | Depending on the applications |
| Numbers | 32-40pcs (Adjustable) |
| Charging Current (max) | 1A ~12A (Adjustable) 12A maximum |
| Charging Voltage | +/-13.65V*N (N = 16~20) |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 40KVA |
| Nominal Power (W) | 40KW |
|
Dimension (D x W x H) (mm) |
797 x 438 x 173 (4U) |
| Weight (kg) | 40 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 400VAC (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage |
3x 360/380/400/415 VAC (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
MANAGEMENT
| Smart RS-232/USB |
Supports Windows, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
BATTERY
| Type | Depending on the applications |
| Numbers | 32-40pcs (Adjustable) |
| Charging Current (max) | 1A ~16A (Adjustable) 12A maximum |
| Charging Voltage | +/-13.65V*N (N = 16~20) |
REAR PANEL
|
GENERAL
| UPS Type | Rack / Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 60KVA |
| Nominal Power (W) | 60KW |
|
Dimension (D x W x H) (mm) |
797 x 438 x 176 (4U) |
| Weight (kg) | 45 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 400VAC (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage |
3x 360/380/400/415 VAC (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
MANAGEMENT
| Smart RS-232/USB |
Supports Windows, Linux and MAC |
| Optional SNMP | Power management from SNMP manager and web browser |
BATTERY
| Type | Depending on the applications |
| Numbers | 32-40pcs (Adjustable) |
| Charging Current (max) | 1A ~16A (Adjustable) 12A maximum |
| Charging Voltage | +/-13.65V*N (N = 16~20) |
REAR PANEL
|