MODEL
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 10KVA |
| Nominal Power (W) | 9KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 83 (without batteries)
210 (w/built-in batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.4 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | 12V 4.5Ah |
| Back-up Time (minutes) | 5 |
| Max. Charging Current | 23.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 15KVA |
| Nominal Power (W) | 13.5KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 88 (without batteries)
212 (w/built-in batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.4 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | 12V 4.5Ah |
| Back-up Time (minutes) | 3 |
| Max. Charging Current | 23.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 20KVA |
| Nominal Power (W) | 18KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 95 (without batteries)
215 (w/built-in batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.4 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | 12V 7Ah |
| Back-up Time (minutes) | 5 |
| Max. Charging Current | 23.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 30KVA |
| Nominal Power (W) | 27KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 113 (without batteries)
310 (w/built-in batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.0% @ 100% load
< 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.2 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | 12V 9Ah |
| Back-up Time (minutes) | 3 |
| Max. Charging Current | 23.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 40KVA |
| Nominal Power (W) | 36KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 120 (without batteries)
400 (w/built-in batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.0% @ 100% load
< 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.2 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | 12V 12Ah |
| Back-up Time (minutes) | 3 |
| Max. Charging Current | 47 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 60KVA |
| Nominal Power (W) | 54KW |
| Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
| Weight (kg) | 185 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.0% @ 100% load
< 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.2 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 47 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 80KVA |
| Nominal Power (W) | 72KW |
| Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
| Weight (kg) | 265 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.0% @ 100% load
< 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 2.8 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 70.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 100KVA |
| Nominal Power (W) | 90KW |
| Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
| Weight (kg) | 290 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.2 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 70.5 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 120KVA |
| Nominal Power (W) | 108KW |
| Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
| Weight (kg) | 290 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.2 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 188 A |
REAR PANEL
|
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 160KVA |
| Nominal Power (W) | 144KW |
| Dimension (mm) | 850 x 900 x 1900 (D x W x H) |
| Weight (kg) | 540 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.0 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 188 A |
REAR PANEL
| 1. Relay interface
2. Emergency Power Off (EPO) 3. RS-232 COM ports 4. Intelligent Slot 5. Input circuit breaker 6. Maintenance bypass switch 7. Output switch 8. Battery switch 10. Parallel port (only available for parallel configuration) |
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 200KVA |
| Nominal Power (W) | 180KW |
| Dimension (mm) | 850 x 900 x 1900 (D x W x H) |
| Weight (kg) | 550 (without batteries) |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 400 V (3Ph+N) |
| Voltage Range | +15% or –20% |
| Frequency Range | 50 / 60 Hz ±5 % |
| Power Factor | 1.0 |
| THDi | < 1.5% @ 100% load
< 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
| Connection Type | Terminal |
| NominalVoltage | 3 x 400 V (3Ph+N) |
| Precision | Stationary: ±1% ;
Transitory: ±2% (load variations 100-0-100%) |
| Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
| Max. Synchronisation Speed | 10 Hz/s |
| Admissible Crest Factor | 3.0 : 1 |
| Harmonic Distortion | < 0.5% (Linear Load)
< 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
| Voltage | 3 x 400V (3Ph + N) |
| Frequency | 50/60 Hz |
BATTERY
| Type | - |
| Back-up Time (minutes) | - |
| Max. Charging Current | 188 A |
REAR PANEL
| 1. Relay interface
2. Emergency Power Off (EPO) 3. RS-232 COM ports 4. Intelligent Slot 5. Input circuit breaker 6. Maintenance bypass switch 7. Output switch 8. Battery switch 10. Parallel port (only available for parallel configuration) |