MODEL
PRO53310-QRS 10KVA
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 10KVA |
| Nominal Power (W) | 10KW |
| Dimension (mm) | 615 x 418 x 132 [3U] (D x W x H) |
| Weight (kgs) | 22 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N+PE) |
| Voltage Range | 190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load |
| Frequency Range | 40 Hz ~ 70 Hz |
| Power Factor | ≧ 0.99 @ 100% load |
| THDi | < 4% @ full linear load |
OUTPUT
| Connection Type | Terminal |
| Output Voltage | 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 |
| Harmonic Distortion | ≦2% THD (Linear load)
≦3% THD (Non-linear load) |
EFFICIENCY & INDICATORS
| AC Mode | 94% |
| ECO Mode | 97% |
| At Full Load | 91% |
| Peak | 92% |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Battery Voltage | ± 12V / 9 Ah |
| Numbers | 16 ~ 20 pcs (adjustable) x 2 |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Charging Current | ± 4A |
PRO53110-QRS 10KVA
GENERAL
| UPS Type | Tower |
| Phase | 3 phase in / 1 phase out |
| Rating (VA) | 10KVA |
| Nominal Power (W) | 10KW |
| Dimension (mm) | 615 x 418 x 132 [3U] (D x W x H) |
| Weight (kgs) | 22 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3 x 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N+PE) |
| Voltage Range | 190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load |
| Frequency Range | 40 Hz ~ 70 Hz |
| Power Factor | ≧ 0.99 @ 100% load |
| THDi | < 4% @ full linear load |
OUTPUT
| Connection Type | Terminal |
| Output Voltage | 208* / 220 / 230 / 240 VAC(L+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 |
| Harmonic Distortion | ≦2% THD (Linear load)
≦3% THD (Non-linear load) |
EFFICIENCY & INDICATORS
| AC Mode | 94% |
| ECO Mode | 97% |
| At Full Load | 91% |
| Peak | 92% |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Battery Voltage | ± 12V / 9 Ah |
| Numbers | 16 ~ 20 pcs (adjustable) x 2 |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Charging Current | ± 4A |