PRO2000LD 2KVA
GENERAL
| UPS Type | Rack |
| Rated Power | 2000VA / 1600W |
| Communication | RS-232/USB and SNMP |
| Dimension (mm) |
400 x 240 x 133 (D x W x H) |
| Net Weight (kgs) | 12.5 |
INPUT
| Nominal Voltage | 120 VAC or 230 VAC |
| Acceptable Voltage Range | 100-130 VAC (Default) or 170-300 VAC
88-152 VAC (AVR Function enabled only available for 120VAC system, adjustable) |
| Frequency Range | 50 Hz/60 Hz (Auto sensing) |
OUTPUT
| Nominal Voltage | 120 VAC or 230 VAC |
| Voltage Regulation (Batt. Mode) | 120 VAC ± 5% or 230 VAC ± 5% |
| Output Frequency | 50Hz/60Hz ± 0.1% |
| THD (Batt. Mode) | <3% @ Full resistive load |
| Efficiency
AC Mode |
95% 90% 87% - 90% |
| Transfer Time
Normal Mode (max.) |
12ms 25ms |
| Waveform | Pure sinewave |
BATTERY
| Nominal DC Voltage | 48 VDC |
| Low DC Warning Voltage | 46VDC ± 0.4VDC @ no load |
| Battery Type | AGM/Gel |
| Charging Current | 2A/4A/6A/8A/10A (Adjustable) |
INDICATORS
| Bypass Mode | Green LED on |
| Battery Mode | Green LED flashing |
| No Output | Green LED off |
| Warning with Output | Yellow LED on |
| Fault without Output | Red LED on |
REAL PANEL
|