MODEL
GENERAL
| UPS Type | Rack |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 10000VA |
| Nominal Power (W) | 9000W |
| Standard Model
Dimension (mm) |
UPS: 668 x 438 x 266 [6U] (D x W x H)
Battery pack: 580 x 438 x 133 [3U] (D x W x H) |
| Weight (kg) | UPS unit: 42
Battery pack: 63 |
| Long-run Model
Dimension (mm) |
668 x 438 x 266 [6U] (D x W x H) |
| Weight (kg) | 42 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 20 (18 - 20 adjustable)** |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | Depending on the capacity of external batteries |
| Charging Current (max) | 4A |
REAR PANEL
|
GENERAL
| UPS Type | Rack |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 15000VA |
| Nominal Power (W) | 13500W |
| Standard Model
Dimension (mm) |
UPS: 668 x 438 x 266 [6U] (D x W x H)
Battery pack: 580 x 438 x 133 [3U] x 2 pcs (D x W x H) |
| Weight (kg) | UPS unit: 42
Battery pack: 63 x 2 pcs |
| Long-run Model
Dimension (mm) |
668 x 438 x 266 [6U] (D x W x H) |
| Weight (kg) | 45 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 20 (18 - 20 adjustable)**x 2 strings |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | Depending on the capacity of external batteries |
| Charging Current (max) | 4A |
REAR PANEL
|
GENERAL
| UPS Type | Rack |
| Phase | 3 phase in / 3 phase out |
| Rating (VA) | 20000VA |
| Nominal Power (W) | 18000W |
| Standard Model
Dimension (mm) |
UPS: 668 x 438 x 266 [6U] (D x W x H)
Battery pack: 580 x 438 x 133 [3U] x 2 pcs (D x W x H) |
| Weight (kg) | UPS unit: 42
Battery pack: 63 x 2 pcs |
| Long-run Model
Dimension (mm) |
668 x 438 x 266 [6U] (D x W x H) |
| Weight (kg) | 45 |
INPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Range | 190-520 VAC (3-phase) at 50% load
305-478 VAC (3-phase) at 100% load |
| Frequency Range | 46~54 Hz or 56~64Hz |
| Power Factor | ≧0.99 @ 100% Load |
OUTPUT
| Connection Type | Terminal |
| Nominal Voltage | 3x 380/400/415 (3Ph+N) |
| Voltage Regulation | ±1% |
| Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
| Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
| Current Crest Ratio | 3:1 (max.) |
| Harmonic Distortion | ≦2% THD (Linear load)
≦5% THD (Non-linear load) |
ALARM & INDICATORS
| Battery Mode | Sounding every 4 seconds |
| Low Battery | Sounding every second |
| Overload | Sounding twice every second |
| Fault | Continuously sounding |
| LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
| Front panel | Status LED, Function keys, LCD display |
| Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
| Standard Model
Type |
12V / 9Ah |
| Numbers | 20 (18 - 20 adjustable)**x 2 strings |
| Typical Recharge Time | 9 hours recover to 90% capacity |
| Long-run Model
Type |
Depending on the capacity of external batteries |
| Numbers | Depending on the capacity of external batteries |
| Charging Current (max) | 4A |
REAR PANEL
|